AVANSA 110Z thermostat
Code: TI_08840181Product detailed description
AVANSA 110Z thermostatThe AVANSA 110-Z thermostat is designed to control the pump for heating and the pump for the DHW storage tank. The heating pump is switched on when the boiler temperature exceeds the user-set boiler switch-on temperature for heating. The DHW storage pump operates based on the temperature difference. The storage tank pump is switched on when the boiler temperature exceeds the storage tank temperature by the set hysteresis. The pump operates until the boiler and storage tank temperatures equalize or the storage tank temperature set point is reached.
Function P (priority) - when this function is active, the DHW storage tank pump operates with priority. The DHW tank pump is switched on first, and when the set temperature of the tank is reached, the heating pump is also started. If this function is deactivated, the pumps operate independently of each other, without priority for the DHW storage tank pump. To activate the priority function, press and hold the MENU button until the display shows the letter P. Then use the arrow keys to select ON (to activate) or OFF (to deactivate) the function.
Function L (summer mode) - switches off the pump for heating, only the DHW tank pump works. The heating pump is only switched on when the boiler temperature exceeds 90°C - this protects the boiler from overheating.
Technical data:
Supply voltage: 230V/50Hz ± 10%
Ambient temperature: -10 to +50°C
Switching current: 6A
Temperature measurement range: 0 to +90°C
Temperature setting range: heating 5 to +80°C, DHW 20 to +80°C
Adjustable reservoir hysteresis: 10 to +30°C
Maximum sensor temperature: -10 to +120°C